Indoor Environment
Connections Featured Writer
Public Library Closes Down For Mold
Investigation
by Rachel L. Adams, Owner, Indoor Management Inc., Greenfield,
Indiana
Last September, Indoor Air Management Inc. was contacted to
perform an on-site inspection of the Westfield Public Library
located in Westfield, Ind. Chronic moisture problems and employee
complaints prompted the request for indoor air quality testing to be
completed. The high moisture levels also raised concerns for the
library's book collection.
The original structure was a one-story, 11,830 square foot
wood-framed building that was constructed in 1983. In 1995, a 12,695
square foot addition was added to the original structure and was
designed to match the original exterior. The exterior cladding
consists of a four-inch-thick stone veneer and the windows are
insulated wood-clad double-glazed windows. The 4/12-pitch roof is a
standard 3-tab fiberglass shingled design. Ventilation vents are
incorporated in the soffits and heat strips are installed on the
West elevation drip edge.
Inspection
The initial inspection revealed significant mold growth and
moisture inside the building. The areas that were most affected were
the West, South, and East exterior walls. There was visible mold
growth present on the wood window trim, behind the cove base of
exterior walls as well as behind vinyl wall coverings that were
peeling from the walls. Visible mold growth was noted on the back
side of the air diffusers in several areas of the library. There was
condensation present on the inside of the wall-mounted fire alarm
boxes as well as water dripping from the window trim of the exterior
West wall.
The moisture readings were collected with a Dri-eaz
nonpenetrating meter and a penetrating Demhorst moisture meter. The
majority of the West wall gave readings of >40 percent, using a
nonpenetrating meter. The South and East walls had several areas of
moisture content above the normal range for those building
materials. Data log devices were placed at several areas of the
library to monitor and record daily temperature and humidity
readings. The readings ranged as high as 80°F and 85 percent RH.
Moisture readings were randomly collected from several books located
throughout the library. The normal moisture content for books kept
in a library institution should be between 6 percent and 8 percent1.
Several books contained a moisture content of >15 percent.
Following the initial inspection, approximately 40 dehumidifiers
were placed in the library, which then removed more than 1,000
gallons of water from the air in the first 24 hours. HEPA air
scrubber equipment was also placed throughout the library to provide
a minimum of four complete air exchanges per hour in an additional
effort to remove contaminants from the indoor environment.
Building Systems
There were several building systems that failed, which
contributed to the excessive moisture inside the building resulting
in mold growth. The evaluation of the building structure by an
engineering firm identified the following primary problem areas:
- Three separate construction errors of the roof caused ice
damming as well as improper attic ventilation
- The one-inch air space that should exist between the stone
veneer and the interior wood framing in the exterior wall
sections had been filled in with mortar, preventing wall
ventilation and resulting in exterior moisture being drawn into
the wall cavity. This condition leads to high interior humidity
levels and creates an unhealthy indoor environment.
- Improper installation of the building windows opened a direct
path for moisture to enter into the building interior.
The evaluation of the HVAC units revealed that one unit could not
effectively remove the moisture from the air, and thus, high
humidity levels throughout the building fostered mold growth.
Samples Collected
A detailed sampling plan was written and followed in order to
provide an accurate assessment of the indoor air quality.
Volumetric Samples
There were 13 volumetric air samples collected from different
locations throughout the library. These samples were collected using
an Andersen-N6, Single-Stage Viable Impact sampler in conjunction
with a high-volume air pump. Samples were collected over a 3-minute
time period at an airflow rate of 1 cubic foot per minute (cfm) and
impacted onto Malt Extract agar for culture. All plates were
incubated at room temperature for 72 to 120 hours before analysis.
Results of volumetric sampling have been reported in colony-forming
units per cubic meter of air (CFU/m3). The rule of thumb for
evaluating air sample data is to compare the types and total
concentration of the indoor samples to the outdoor reference sample.
What is identified in the indoor environment should be very similar
to what is found in the outdoor sample. This is because of mold
entering the indoor environment through HVAC systems and through
doors and windows, and mold being carried into the indoors by
occupants. The concentrations of total mold found indoor samples
should be significantly less than what is identified in the outdoor
reference sample because most indoor environments are at a slightly
positive pressure due to heating and cooling of the indoor space.
It is important to remember that air samples are only a snapshot
of the indoor conditions at a specific time of day, activity level,
and season of the year. These results will vary with changes in the
environment and are only used as a diagnostic tool for evaluating
the indoor air quality and possible toxic exposure issues. In the
case here, the outside reference sample contained a total fungal
concentration of >30,923 CFU/m3, with Cladosporium spp.
predominating. Also identified was Alternaria spp., Epicoccum spp.
and a small amount of Penicillium spp.
Although the total concentration is high, the types of mold
identified is typical for outdoor air. In the samples collected
throughout the library, Penicillium spp. was the predominant mold
identified, and in six samples, it was the only mold type
identified. This indicates an imbalance in the indoor air allowing
growth of an indicator species of mold.
Surface Contact Samples
Several surface samples were collected by pressing Rodac surface
plates containing Malt Extract agar onto a selected area containing
visible mold growth. The four molds identified from several areas of
the library were Penicillium spp., Aspergillus nidulans, Aspergillus
niger and Stachybotrys chartarum. The majority of these samples were
collected from visible mold growth on the window trim, behind cove
base, inside wall cavities and behind vinyl wall coverings.
Bulk Samples
Several bulk samples were collected and consisted of drywall,
insulation, vinyl wall coverings and insulation from inside the HVAC
unit. All samples were reported as >50 CFU/in2 due to excessive
growth. The primary molds identified from these building materials
were Penicillium spp., Aspergillus niger, Aspergillus nidulans,
Pithomyces spp. and Stachybotrys chartarum.
Surface Swab Samples
Sterile swabs were used to collect samples from different
surfaces such as air diffusers, inside air duct louver, behind cove
base and from library books. All samples were reported as >200
CFU/in2 with Penicillium spp. as the predominant fungi. Also
identified was Curvularia spp., Acremonium spp., Acremonium spp.,
and Cladosporium spp.
Air-O-Cell Cassettes
There were six samples collected using a unique sampling device
designed for the rapid collection and analysis of a wide range of
airborne particles, including fungal spores. Samples are analyzed
via light microscopy at 600x magnification in which the entire
sample is analyzed and reported as a total (viable and nonviable
spores). Although this sampling technique does not allow for the
differentiation between Penicillium and Aspergillus species, it does
allow for the identification of Stachybotrys. The types of molds
identified in the samples collected throughout the building were
Penicillium/Aspergillus and Stachybotrys.
Mycotoxin Analysis
There were several library employees who had experienced health
effects that were suspected to be related to a toxic mold exposure.
It was requested that samples be collected for mycotoxin analysis
and used for medical evaluations. The samples collected for this
analysis were bulk samples that came from areas containing the
heaviest amounts of mold contamination in air samples. These areas
presented the highest risk for a toxic exposure to the employees as
well as the patrons. The samples were taken through an extraction
process to recover any mycotoxins present. They were then analyzed
by HPLC (high-performance liquid chromatography) for identification
and quantification.
Mycotoxins are nonvolatile, relatively low-molecular weight
secondary metabolic products that may affect exposed persons in a
variety of ways. These compounds are considered secondary
metabolites because they are not necessary for fungal growth and are
simply a product of the primary metabolic processes. The functions
of mycotoxins have not been clearly established, but they are
believed to play a role in eliminating other microorganisms
competing in the same environment. They are also believed to help
parasitic fungi invade host tissues2. The amount of toxins needed to
produce adverse health effects varies widely among toxins, as well
as each person's immune system.
Fungi that produce mycotoxins are referred to as toxigenic fungi.
The most frequently studied mycotoxins are produced by species of
Aspergillus, Fusarium, Penicillium, Stachybotrys and Myrothecium.
However, toxins have been detected from many other fungi under
certain growth conditions. The kinds and amounts of toxin produced
depend on the fungal strain, the growing conditions, as well as the
presence or absence of other organisms. Mycotoxins accumulate on
fungal spores, cell fragments, and substrates (nutrient source).
Fungi that produce potent mycotoxins are seldom abundant in
outdoor ambient air. Most toxic exposures occur from indoor growth
of fungi related to excessive moisture. Some mycotoxins are
carcinogenic, some are vasoactive, and some cause central nervous
system damage. Often, a single mycotoxin can cause more than one
type of toxic effect.
In the library, the mycotoxins present in the greatest
concentrations were Sterigmatocystin, Satratoxin H and Roridin E.
Although there were 14 target compounds identified as the primary
mycotoxins of interest, there were other tentatively identified
compounds (TICs) that were also present, such as Atranones, Mytoxins
and Stachybotryamides.
Remediation Protocol
Indoor Air Management Inc. was contracted by the library board of
directors to provide the remediation protocol for the remediation
company to follow, as well as to monitor the project to ensure a
successful outcome. The remediation recommendations are summarized
as follows:
- The remediation must be completed by professionals that have
experience and are trained in the safe and effective removal of
microbial contamination. They must also have an internal safety
/ respirator program in place to ensure all personnel are
trained in the proper use of personal protective equipment (PPE)
as required by OSHA.
- All personnel performing the remediation must wear full PPE.
- Books must be processed through a completed cleaning procedure
that includes HEPA vacuuming. Any books with a moisture content
higher than that recommended by MBK consulting must be dried to
a normal moisture content prior to pack-out and storage.
- The HVAC system must be disabled with critical barriers in
place on all registers and vents. Any insulated ductwork must be
removed and replaced with galvanized metal ducts along with a
complete maintenance schedule for all units. The Specifications
stated in the HVAC report provided by the ventilation expert
must also be implemented.
- Control of the humidity and temperature in the building must
be maintained during the entire remediation project3. The
remediation contractor is responsible for providing the
equipment and monitoring protocol to achieve, maintain, and
monitor the indoor conditions.
- Containment erected from 6-mil polyethylene sheeting and/or
temporary walls will be constructed to contain all contamination
inside the contained areas. A partial pressure differential of 5
- 7 pascal will be used to establish and maintain the contained
area. The floor plan provided by the library was used to
determine how the building is sectioned off for erection of
containment.
- All porous materials that are supporting mold growth will be
removed and disposed of in double 6-mil plastic bags prior to
removal from the building. The porous materials include but are
not limited to drywall, cove base, insulation, wood trim,
ceiling tiles and carpet.
- Following the complete removal of all contaminated building
materials, a HEPA "sandwich" cleaning protocol will be
performed which includes HEPA vacuuming and damp wiping with a
detergent and minimal water. Wood framing must be cleaned by
means of an abrasive technique such as sanding or wire brushing
followed by drying to a normal moisture content.
- Following the completion of the remediation procedures, the
structural components must be analyzed and corrections should be
recommended by the structural engineer contracted to correct the
structural flaws. It is critical for these corrections to be
identified and implemented to prevent a re-occurrence of these
same moisture problems.
The remediation of this public library is currently in progress.
A follow-up of containment photographs as well as verification
sample results and structural modifications will be presented in a
subsequent article. It is very important that all of the appropriate
experts participate in a remediation project to ensure the complete
and safe removal of mold-contaminated materials. The liability
issues that are a normal part of these projects are greatly
minimized by establishing the correct protocols and ensuring they
are completed. Verification samples at the completion of the project
can provide the remediation professional as well as the IAQ expert
with final assessment of a successful remediation.
References
- "The Effect of Moisture on Paper", Helen U. Kiely,
March 5th, 1927, American Writing Paper Co.
- Bioaerosols; Assessment and Control; ACGIH, Cincinnati, OH
1999
- IICRC Standard and Reference Guide for Professional Water
Damage Restoration, S500 - Second Edition, Vancouver, WA 1999
Rachel L. Adams is vice president of MSA Restoration and owner of
Indoor Air Management Inc. in Greenfield, Ind. She has provided
technical consulting, sampling services and education for indoor air
quality and mold remediation projects over the past five years. She
is also currently involved with Bolden's Manufacturing and the
research associated with the innovative Hydrolab. The research will
test and measure microbial contamination of different building
materials in water-damaged structures. You can reach her by calling
(317) 894-0861.
|
|
Certification Arrives For Mold Work
While there continues to be an influx of new training courses on
mold and microbial issues, the American Indoor Air Quality Council
(AmIAQ) recently set the bar up a notch and introduced the industry's
first certification for mold remediation.
The Certified Mold Remediation Supervisor (CMRS) program
specifically addresses the mitigation and/or remediation of molds,
bacteria, yeast, etc. found in buildings. CMRS applicants will be
required to have two years experience in microbial or a similar
remediation field. including conducting IAQ microbial investigations,
doing mitigation/remediation spec writing, performing project
management tasks and, of course, conducting the actual mitigation
and/or remediation.
The first study/review course and examination was to be held at the
end of this month in Syracuse, N.Y., with a second course to be held
next month in Orlando, Fla., Feb. 9-11. Both courses will be conducted
by Bob Krell, president of IAQ Technologies Inc in Syracuse. In
addition, there will be three other AmIAQ-approved training centers
will provide study/review materials and proctor the examination.
According to Charles Wiles, executive director of AmIAQ, the other
training providers will be announced next month.
"This certification examination was developed 'from the ground
up' as a microbial remediation certification," Wiles told IE
Connections. "Training providers will develop all new
study/review courses that specifically address microbial
remediation."
The 20-hour CMRS course will cover basics on microbial assessment,
project design and monitoring and public relations, but the primary
focus will be on remediation.
The CMRS examination will be a four-hour examination of 100
questions, each question having five possible answers. "It will
be very difficult for the inexperienced to pass," Krell told IE
Connections.
The 20-hour class will encompass the information covered on the
certification exam, along with a wealth of practical knowledge for
practitioners. The CMRS program is geared towards individuals with
basic knowledge and experience in either microbial remediation or a
related field.
For more CMRS information or to register for next month's course,
call IAQ Technologies at (800) 788-2446 or go to www.iaqcouncil.org.
|
|
EPA Updates Radon Risk Data In New Home Guide
by Douglas Kladder, President, CVC, Inc., Colorado Springs,
Colorado
Last November, EPA released a revised edition of the their Home Buyer's
and Seller's Guide. This document has been one of the primary tools that
real estate professionals have used in disclosing information about radon
at the time of sale. It has also been a tool that many radon professionals
have used in providing information to prospective clients.
Although much of the document remains unchanged from its earlier 1993
edition, EPA has updated the health risk data to reflect recent radon risk
estimates:
"Based upon information contained in the National Academy of
Science report, The Health Effects of Exposure to Indoor Radon, radon is
estimated to cause between 15,000 and 22,000 lung cancer deaths per
year".
This represents a significant increase (as much as 57 percent) over the
14,000 annual U.S. death rate reported in the previous guide.
Homebuyers will find an expanded section regarding the advisability of
having radon control techniques incorporated into the construction of new
homes.
However, there are a few new items that will be of specific interest to
radon professionals since they do not appear to be within current EPA
protocols:
The guide suggests new tests be conducted if the previous tests were
not conducted within two years before the sale of the property.
The guide also indicates a prohibition of testing in hallways of
residential structures, which is not a criterion within current testing
protocols.
In the section regarding methods for preventing or detecting test
interference, the new guide suggests "proximity detectors to reveal
the presence of people in the room which may correlate to possible changes
in radon levels." In addition to conjuring up images of "Big
Brother", does such a device exist for radon use? If someone is aware
of it, please email me and we will report on it in a future article.
Perhaps the most striking aspect of the new Home Buyer's and Seller's
Guide is the absence of referrals to EPA's now closed radon proficiency
program. Buyers and sellers are advised to contact state radon offices
rather than national certification boards.
An html version of the document is at: www.epa.gov/iaq/radon/pubs/hmby
guid.html
Other Radon Program Updates: New Device Evaluation Program
The first manufacturer to submit a new radon measurement device through
the National Environmental Health Association's new Device Evaluation
Program has successfully completed this rigorous review. Onguard Systems,
a manufacturer of blind and non-blind continuous radon monitors, received
NEHA approval last month. NEHA certified individuals and laboratories may
now submit these devices for performance testing and certification.
Continuing Education
As part of NEHA's commitment to work more closely with training
providers, a new procedure was put into place last month whereby all
training providers can update and submit their curriculum for approval for
use by individuals certified by the National Environmental Health
Association's National Radon Proficiency Program in renewing their
credentials.
Several aspects of this procedure are an enhancement of old EPA
approaches. Course reviews by attendees will be posted on NEHA's website
and review criteria for distance based courses have been better defined.
All currently NEHA approved continuing education courses will expire as of
Feb. 28, 2001 unless they are submitted for review before that date.
Performance Test Chamber Added To List
Blind performance testing was an integral part of EPA's former
proficiency program and is a requirement of current national proficiency
programs. A second performance test chamber, Radon Measurements Lab, joins
Bowser-Mourner as a NEHA certified chamber for blind performance testing.
Chambers achieving this certification must have rigorous radon or radon
decay product measurement procedures and quality control measures in
place, and routinely inter-compare with EPA chambers. Although NEHA
approved, individuals should verify chamber certification with some
states.
Doug Kladder is president of CVC Inc. in Colorado Springs, Colo., which
is contracted to administer the NEHA, NRPP and the Western Regional Radon
Training Center. You can reach him by calling (719) 632-1215 or by e-mail
at dougkladdr@aol.com.
|